| Installation description for LA39-A series pushbutton |
|
 |
Insert the operator in the mounting hole from the front of panel,then twist in the bracket from the back of panel.
Fasten the screws(not too stong,max.torque is 25N-cm).When the panel is plastic and other non-metal material,F5
(refer to page 14))can be put at the back of of the panel.When the mounting hole is 25mm,F6 (refer to page 14) can
be put at the back of mounting panel.
For Z1 type,the contact block can be mounted together with bracket.
For Z2 type,the contact block should be disassembled ,then assemble the bracket.
For Z3 type,the contact block should be disassembled,then insert the bracket into the operator, clockwise the
bracket and tighten the nuts in the bracket.
Note: lf it doesn't work smoothly after mounting,please adjust both tightening screws to keep balance. |
|
 |
Contact block can be directly fastened,the
symbol parts can be mounted in the front of
panel.Please fasten lamp holder before the
contact block as mounting illuminated buttons.
Note:Please check the buckles of contact
block after mounting. |
|
 |
Disassembly the contact block and lamp
holder,please srewdriver to lift the buckles
of the mounting system.The mounted
parts can be easily disassembled. |
|
|
| Note:When mount the selectors,the white dots of short-knob and acumination of long-knob should be put upwards. |
|
Normal pushbutton,illuminated pushbutton
key selector and selector |
 |
|
| Mushroom pushbutton and long lever selector |
 |
|
Note:Min mounting hole distance is 35 x 50 as bracket is Z3. |
|
Using 2-digit figure:the first digit : 1,2 shows the contact block , 3,4 shows the contact position.
the second digit : 1,2 means normally close, 3,4 means normally open. |
| Function diagram of selectors and key selectors |
|
 |
| |
| |
|
|
|